TEK-AIR FLOWMETER - IAQ2000 SERIES - OUTDOOR AIR MEASUREMENT SYSTEM

 

The IAQ Outdoor Air Measurement system is designed for accurate measurement in outdoor air inlet situations where low velocity, dirt, moisture and turbulence affect other products in quantifying the volume of fresh air to the building. The IAQ utilizes a Patented air flow sensor in conjunction with a transducer and monitor assembly, which incorporates intuitive directions for the user in setting up and maintaining the product.

Tek-Air IAQ2000 Series

Applications
After inlet louvers on an outdoor air inlet
Under the rain hood of roof top units
Large ducts with low velocities

Advantages
Velocities as low as 60 fpm
Not affected by moisture
Large areas with low velocities
Works in turbulent air
Stable transmitter output
User friendly

Tek-Air IAQ2000 Series Application

 

PRODUCT INSTALLATION

Tek-Air IAQ2000 Series Installation

 

SPECIFICATION OF IAQ-2000 SERIES :
System Accuracy
Velocity for 0.1" transducer
200 to 1000 fpm; +/- 5% reading
75 to 200 fpm; +/- 10% reading
Higher ranges available. Consult your local
representative for more information.


Probe and Transducer
Temperature
Operating: -40 to 120°F
Storage: -40 to 150°F
Air Velocity Capabilities
Discharge of intake louver - 75 to 750 fpm
Free air, before damper - 100 to 1000 fpm
Probe
Material: PVC/ABS
Fire rating: UL-94-VO and UL-94-5VB
Size: 8.5" diameter, 7.5" depth
Weight: 1.5lbs.
Tubing connections: 1/4" barb fittings
Transducer
Enclosure: NEMA-4X water tight
Enclosure size: 6" W x 4.75" H x 3.5" D
Mounting footprint: 7.5" W x 4.75" H
Weight: 1.5 lbs.
Tubing connections: 1/4" barb fittings
Electrical connection: Factory provided integral cable


Monitor
Temperature
Operating: 30 to 110°F
Storage: -40 to 150°F
Enclosure
Type: NEMA-4X water tight
Size: 9" W x 9.5" H x 3.5" D
Mounting footprint: 9.0" W x 9.5" H
Weight: 3.5 lbs.
Power
Supply voltage: 24 VAC, limits 19 to 31 VAC
Power: 25 VA
Digital Input for Fan Status Interlock
Type: Dry Contact
Analog Outputs
Type: Powered and isolated 4-20mA
Scaling:
cfm: user set
temp: -30° to 120°F
Output load: 0-600 ohms
Digital Alarm Output
Type: dry contact, SPDT
Rating: 0.5 amps max.
State: normally energized
Display
Type: LCD, backlit
Size: 4 lines - 20 characters per line

 

 