TEK-AIR FLOWMETER - Iso-Tek SPM2000 SERIES - SPACE PRESSURIZATION MONITOR SYSTEM FOR ISOLATION ROOMS AND LABORATORIES

 

The Iso-Tek space pressurization monitoring system is designed for use in a wide variety of applications that necessitate the monitoring of airflow from one room to another. The monitor system can be configured by the user for bi-directional measurement of either air velocity in feet per minute (fpm), or air pressure in inches of water column ("wc").

Tek-Air SPM2000

Space Pressurization is required in Hospitals, Laboratories, Clean Rooms and Pharmaceutical Production Areas. Tek-Air’s Iso-Tek space pressurization monitor is designed specifically for the continuous monitoring of the space differential pressure for these and other critical applications.

.Applications

Hospitals, including patient isolation, autopsy and operation rooms
Prisons and shelters
Chemical laboratories


Advantages

Continuous monitoring at a fraction of the cost of manual techniques
Meets ANSI and AIHA Lab Safety Standard, Z9.5-1992
Rugged construction
Fewer installation constraints
Immunity to fouling by lint and dirt

 

Monitor System Components

Tek-Air SPM2000 Installation

 

Specifications
Velocity Range : -1000 to +1000 fpm, full scale range adjustable to +/- 100, 250, 500, or 1000 fpm
Pressure Range : -0.100 to +0.100 "wc, full scale
Accuracy : Pressure: +/- 2% of set range, Velocity: +/- 10 fpm
Analog Resolution : Pressure: 0.0001 "wc . Velocity: 1.0 fpm
Digital Resolution : +/- 0.5 fpm, +/- 0.00005 "wc
Airflow Polarity : Selectable for Positive, Negative, Neutral, or Standby
4-20mA Output : Self-powered, 500load maximum, Neutral is 12mA
Power Supply : 24VAC, +/- 4V, <10VA
Communications : RS-485, half duplex, Open Protocol, N2 compatible available upon request
Alarm Contacts : SPDT, 0.5A max.

 

 

Back to previous page (Kembali ke halaman sebelumnya)